Fitur Utama
Omah digawe saka serat kaca poliester sing diperkuat (GRP)
Diffuser PC transparan lan tahan impact dhuwur
Mode standar lan darurat kasedhiya
Sistem pemanasan otomatis kanggo operasi ing suhu sing adhem banget nganti -40 ° C
IP65
Spesifikasi Item. | LL02H210 | LL02H218 | LL02I210 | LL02I218 | LL02J210 | LL02J218 |
Kode | LL02H210-6 | LL02H218-6 | LL02I210-4/6 | LL02I218-4/6 | LL02J210-4/6 | LL02J218-4/6 |
Nomer Barang GE | 445W2449P001 (120-230V), 445W2449P004 (100V)445W2449P006 (120-230V) | 452W5645P001(1 kelenjar kabel)452W5645P002(2 kelenjar kabel) | 445W2449P002 (120-230V),445W2449P005 (100V)445W2449P007 (120-230V) | 445W2449P003 (120-230V) 445W2449P008 (120-230V) | 452W5645P003(1 kelenjar kabel)452W5645P004(2 kelenjar kabel) | |
Katrangan | Cahya, LED, Standar SW/CW | Lampu, LED, Cadangan Darurat, SW | Lampu, LED, Cadangan Darurat, Sistem Pemanas, CW | |||
Tegangan Input | 120-277V | |||||
Range Tegangan | 100-300V | |||||
Frekuensi | 50-60Hz | 50-60Hz | 50-60Hz | 50-60Hz | 50-60Hz | 50-60Hz |
Dirating Daya Input | 23W | 45W | 23W | 45W | 23W | 45W |
30.5W (Pekerjaan Sistem Pemanasan) | 52.5W (Pekerjaan Sistem Pemanasan) | |||||
Nominal saiki | 0.19A | 0.38A | 0.19A | 0.38A | 0.19A | 0.38A |
0.26A | 0.44A | |||||
Suhu Operasi | -35~55°C | -35~55°C | -5~55°C | -5~55°C | -35~55°C | -35~55°C |
Survival Temp. | -40~60°C | -40~60°C | -15~60°C | -15~60°C | -40~60°C | -40~60°C |
Tipe Lampu | LED SMD, Putih Keren | |||||
Lumen Output | 2100lm | 3700lm | 2100lm | 3700lm | 2100lm | 3700lm |
Wektu Darurat | N/A | N/A | > 90 Min | > 90 Min | > 90 Min | > 90 Min |
Umur baterei | N/A | N/A | 5 taun | 5 taun | 5 taun | 5 taun |
Meas.Saka cahya | L 670mm x W 164mm x H 102mm | L 1275mm x W 161mm x H 102mm | ||||
Jarak pemasangan | 400±5mm | 984±5 mm |
** Kode No. LL02H210-X, nalika X=2: CE disetujoni;X=4: UL disetujoni;X = 6: CE + UL disetujoni.
LL02H210/LL02I210/LL02J210:
kadohan soyo tambah (LF): 400±5mm 2pcs soyo tambah bolongan siap kanggo M6 bolts.
LL02H218/LL02I218/LL02J218:
Solusi Pemasangan 1
kadohan soyo tambah (LF): 984±5mm 2pcs soyo tambah bolongan siap kanggo M6 bolts.
Solusi Pemasangan 2
kadohan soyo tambah (LF): 800±5mm 2pcs soyo tambah bolongan siap kanggo M6 bolts.
Ilustrasi pemasangan:
Phenix Part Number | Nomer Bagian GE | Jumlah kelenjar | Lokasi kelenjar | Jumlah plug dummy |
LL02H210/LL02I210/LL02J210 | 445W2449P001-445W2449PP005 | 2 | Ing mburi jejere siji liyane | 1 |
LL02H210/LL02I210/LL02J210 | 445W2449P006-445W2449P008 | 3 | Loro ing mburi jejere saben liyane Katelu ing mburi ngelawan saka loro kelenjar liyane | 0 |
LL02H218/LL02I218/LL02J218 | 452W5645P001/452W5645P003 | 1 | Ing mburi cedhak blok terminal | 0 |
LL02H218/LL02I218/LL02J218 | 452W5645P002/452W5645P004 | 2 | Siji ing saben pungkasan | 0 |
1 (utawa 2) kelenjar kabel ing sisih siji
1 utawa (0) kelenjar kabel ing sisih liyane
Klip ora tiba
Sistem pemanas digunakake kanggo mesthekake luminaire bisa digunakake kanthi apik ing cuaca sing adhem nganti -40 ° C.
Tegangan Input: 120-277V
Kanggo lampu darurat (utawa darurat + pemanasan), tes lan pangopènan ing ngisor iki kudu ditindakake:
Pencet Ngalih Test LED (TSW) kanggo ngganggu daya kanggo mimpin driver darurat lan meksa luminaire menyang mode darurat, lampu Strip LED saiki lagi surem ing cahya suda;lampu sinyal LED (LSL) ing TSW dipateni ing mode darurat.Sawise ngeculake TSW, luminaire bali menyang operasi normal sawise wektu tundha sedhela, lampu Strip LED surem kanthi daya lengkap, lan LSL diuripake.
Saklar Tes LED (TSW)
Cathetan: Yen pangguna pungkasan mbutuhake luminer kanggo pindhah menyang mode darurat mung nalika daya listrik gagal, saklar eksternal kudu ditambahake ing terminal input.
Sawise nginstal saklar eksternal, luminer kudu dites (status urip lan mati) yen cocog karo kahanan ing ngisor iki:
Nalika daya listrik urip:
Nguripake ngalih njaba, luminaire ing mode normal: Kabeh lampu Strip LED murup, lan LSL surem, lan baterei lagi kebak.
Pateni saklar eksternal, luminer ing mode normal: kabeh lampu strip LED mati, LSL murup, lan baterei lagi diisi.
Nalika pasokan listrik gagal:
Ora ketompo yen ngalih eksternal diuripake utawa dipateni, luminer dadi mode darurat.Kabeh lampu strip LED diuripake ing output suda.LSL mati lan baterei wis kosong.
1. Tes Otomatis Langsung
Nalika sistem disambungake kanthi apik lan diuripake, luminer bakal nyoba kanthi otomatis yen muatan lan baterei wis disambungake kanthi apik lan yen baterei diisi kanthi normal.Yen ana kahanan sing ora normal, Lampu Sinyal LED (LSL) kelip-kelip.Nalika abnormity dibusak, LSL nuduhake biasane.
2. Preprogrammed dijadwal Auto Test
– Nindakake Tes Otomatis saben wulan pisanan sawise daya wiwitan urip sajrone 24 jam nganti 7 dina, banjur nindakake Tes Otomatis saben wulan saben 30 dina.
– Nindakake Auto Test taunan saben 52 minggu sawise pisanan powered on.
- Wektu Tes Otomatis
Kanggo nyuda konflik sing Tes Otomatis ditindakake nalika lampu digunakake, Tes Otomatis sing wis diprogram bakal dileksanakake 2 jam mengko saka operasi normal sing dicopot (pateni).Kanggo aplikasi sing lampu tetep madhangi, modul kasebut bakal nundha tes sing dijadwalake, nanging ora luwih saka wektu tes paling anyar sing dijadwalake.
- Tes Otomatis Saben wulan
Tes Otomatis Saben wulan kudu ditindakake saben 30 dina lan kanggo nyoba:
Yen switchover saka mode normal lan darurat normal;
Yen fungsi darurat lan kondisi pangisi daya lan discharging baterei normal;
Wektu Tes Otomatis kira-kira 30 detik.
- Tes Otomatis Taunan
Tes Otomatis Tahunan kudu ditindakake sawise ngisi daya lengkap 24 jam lan kanggo nyoba:
Yen voltase baterei padha utawa luwih saka watesan sawise 24 jam ngisi daya lengkap;
Yen wektu operasi darurat luwih saka 90 menit;
Yen voltase baterei sawise 90 menit operasi darurat isih padha utawa dhuwur saka 87,5% saka voltase baterei sadurunge testing.
– Sajrone Tes Otomatis, yen ana gangguan daya lan daya ora bisa urip nganti Tes Otomatis rampung, banjur Tes Otomatis bakal dileksanakake maneh 24 jam mengko sawise daya urip.
– Yen mode darurat nggawe baterei kosong ing kondisi mati, banjur Tes Otomatis sing wis diprogram bakal diterusake maneh nalika daya disambungake.
3. Tes Manual
– Pencet LED test switch (LTS) sapisan, banjur pindhah menyang mode darurat lan bali menyang mode normal kanthi cepet.
- Pencet LTS 2 kaping terus-terusan sajrone 5 detik, banjur tes saben wulan.Sawise rampung, tes saben wulan sabanjure bakal diitung wiwit tanggal kasebut.
- Pencet LTS kaping 3 terus-terusan sajrone 5 detik, banjur mlebu tes taunan.Sawise rampung, tes taunan sabanjure bakal diitung wiwit tanggal kasebut.
- Sajrone tes manual, penet LTS kaping 3 sajrone 5 detik, banjur tes manual bisa diakhiri.(Waktu Tes Otomatis sing wis dijadwalake ora bakal ganti)
4. Indikator LED Signal Lamp (LSL).
- LSL ing: Normal
– LSL mati: Gagal daya
– LSL owah-owahan bertahap: Ing testing
– LSL kelip-kelip: Abnormal
Ora. | Item No | Karton njaba L(CM) | Karton njabaW(CM) | Karton njabaH(CM) | Qty/CTN (PCS) | NW/CTN (KGS) | GW/CTN (KGS) | |
1 | LL02H210 | 70 | 37 | 25.5 | 4 | 16.5 | 18.2 | |
2 | LL02H218 | 130.5 | 37 | 25.5 | 4 | 19.8 | 21.3 | |
3 | LL02I210 | 70 | 37 | 25.5 | 4 | 17.7 | 19.4 | |
4 | LL02I218 | 130.5 | 37 | 25.5 | 4 | 20.8 | 22.3 | |
5 | LL02J210 | 70 | 37 | 25.5 | 4 | 18.5 | 20.4 | |
6 | LL02J218 | 130.5 | 37 | 25.5 | 4 | 21.5 | 22.8 |